Auto Detuned Filter Bank

FT1000 Series

Medium & H.V. Automatic Detuned Filter Bank

Power transmission and distribution systems are designed to operate with sinusoidal voltage and current waveforms at a constant frequency. However, when nonlinear loads, such as thyristor drives, converters and arc furnaces are connected to the system, excessive harmonic currents are generated, causing both current and voltage distortion. When harmonics are presented in the system, power factor correction should be implemented by means of automatic capacitor banks with detuned reactors. Each step of the bank consists of a capacitor unit with an anti-resonant LC circuit. It forms a resonant circuit series tuned to a frequency below the 5th harmonic.

 

 

Caractéristiques techniques :

Color

Grey ASA61

Construction Standards

UL, CSA

Continuous over-current

150 %

Continuous over-voltage

120 %

Detuned Frequency

7 % or 12.6 % (other tuned

frequency on request)

Enclosure Type

Indoor, Outdoor

Insulation Level

60, 75, 95, 125 kV BIL

Mounting Type

Floor Mounting

Power Factor Controller

N12 or NC12, 12 steps

Power Losses

0.4 W/KVAR

Rated Frequency

50 Hz or 60 Hz

Rated Power

20 to 6000 KVAR/Unit

Rated Voltage/Phase

2400 @ 2500 volts/3 Phases

Temperature Class

Average 24h

-40° C to 45° C

+35° C

Tuned Frequency

5th, 7th, 11th and 13th