You are here : Gentec > Data Acquisition Systems > PES3/UAT > PES3 - Specifications
| System Specifications | |
|---|---|
| Capacity | |
| Up to 16 shelves | |
| Up to 17 input and/or output cards per shelf | |
| Up to 8704 input and /or output points per system | |
| CPU | |
| 32-bit Motorola MPC860T | |
| 32Mb SDRAM | |
| Power Supply | |
| 105Vdc-140Vdc or 108Vac-132Vac | |
| Simple or double power supply | |
| Communication Ports | |
| Port RS-232 (1x) - Maintenance | |
| Port RS-232 (2x) – Remote access | |
| Port Ethernet 10Base-T or 100Base-TX/FX | |
| IRIG-B synchronization input | |
| Others | |
| Visual indicators (DEL) for each input-output point | |
| Input/Output Card Specifications | |
|---|---|
| Analog Input Cards | |
| 16x differential insulated inputs | |
| Input range: ±2.56Vdc and ±10.24Vdc | |
| Precision of 0.2% | |
| Self-sampling | |
| Fast Analog Input Card | |
| 16x differential insulated inputs | |
| Input range: ±140Vac/1mA/4-20mA | |
| Precision of 0.1% | |
| Self-sampling | |
| Variable sample from 1 to 100kHz | |
| Digital Input Cards | |
| 32x optically insulated inputs | |
| Programmable filter 2ms—65ms | |
| Sampling at 500uS | |
| Relay Output Card | |
| 16x insulated relay outputs | |
| 5A form-C Contacts | |
| Pre-selected mode (SBO) | |
| Mechanical Specifications | |
|---|---|
| Enclosure size (HxLxD) | |
| UAT | 265.9x482.6x316.0mm (10.5”x19”x12.4”) |
| Material | Aluminum |
| Color and finish | Aluminum & black mat |
| Environmental Specifications | |
| Temperature | |
| Operating | -25 oC—55oC (-13oF—131oF) |
| Storage | -40 oC—85 oC (-40oF—185oF) |
| Humidity | 0-95% non-condensing |
| Cooling | Natural or forced convection |
| Altitude | 0% @ 0-3300 feet (1000m) |
| Standards | |
| Environmental | IEC 60068-2-1 /-2 /-3 |
| Fire resistance | UL 94V-0 |
| Shock and Vibration | IEC 60255-21-1 |
| SWC | IEC 60255-22-1 /-4 |
| Dielectric strength | IEC 60255-5 |
| ESD | IEC 61000-4-2 |
| EMC Radiated/Conducted | IEC 61000-4-3 /-6 |